Standard Damper Actuators

Standard Damper Actuators

Standard Damper Actuators

The F30A series is designed for precise control of air volume and direction in commercial and industrial ventilation systems. As non-spring return actuators, they hold their position when power is removed, making them suited to modulating and on/off duties where a defined fail-safe position isn't required. Three variants are available — standard, low noise, and fast running — sharing a common mounting arrangement and control platform, so specifiers can select on performance without changing installation approach.

F30A Series Standard Damper Actuator

Choosing Your Variant

Use this to identify which variant suits the application, then see the full specification for each below.

  Standard Low Noise Fast Running
Torque 2–40 Nm 2–10 Nm 5–16 Nm
Running time 35–100 s 75–150 s 2.5–8 s
Noise level ≤45 dB ≤35 dB 55–60 dB
Life cycle ≥70,000 ≥70,000 ≥30,000
Certification CE, UKCA, UL, RoHS CE, UKCA, RoHS CE, UKCA, RoHS
Best for General HVAC Noise-sensitive spaces Rapid response

F30A Series Standard Damper Actuator

The core actuator for everyday HVAC applications, covering six torque ratings and damper areas up to 8 m².

Find out more technical details about our F30A

Standard damper actuator

 

Torque and Running Time

Torque Damper area Running time Weight
2 Nm 0.5 m² 35 s 0.5 kg
5 Nm 1 m² 45 s 0.5 kg
10 Nm 2 m² 60 s 0.9 kg
20 Nm 4 m² 75 s 0.9 kg
30 Nm 6 m² 75 s 1.4 kg
40 Nm 8 m² 100 s 1.4 kg

Specification

  • Supply voltage: AC/DC 24 V (19.2–28.8 V) or AC 230 V (85–265 V), 50/60 Hz
  • Control: 2/3 point, or modulating 0(2)–10 V / 0(4)–20 mA
  • Power consumption: 1.5–5 W in operation, 0.7–1 W at rest
  • Angle of rotation: 0–90° (max 93°), L/R switchable
  • Position feedback: None or 2 SPDT
  • Protection: IP54, class II/III
  • Ambient: −30 to +50 °C, 5–95% RH
  • Life cycle: ≥70,000
  • Spindle: 8–18 mm (2/5 Nm) · 12–26.7 mm (10–40 Nm)
  • Certification: CE, UKCA, UL, RoHS

Order Code

F30A – [torque] [control] [voltage] – [accessory]

Control: D = 2/3 point, M = modulating. Voltage: 24 = AC/DC 24 V, 230 = AC 85–265 V. Accessory: S = auxiliary switches.

Example: F30A-10M24-S — 10 Nm, modulating, 24 V, with auxiliary switches.


F30A Series Low Noise Damper Actuator

Where acoustic performance matters — offices, hotels, healthcare, education — this variant runs at ≤35 dB, a 10 dB reduction from the standard unit.

Find out more technical details about our F30A-L

F30A Series Low Noise Damper Actuator

Torque and Running Time

Torque Damper area Running time Weight
2 Nm 0.5 m² 75 s 0.5 kg
5 Nm 1 m² 150 s 0.5 kg
10 Nm 2 m² 150 s 0.9 kg

Specification

  • Noise level: ≤35 dB
  • Supply voltage: AC/DC 24 V or AC 230 V, 50/60 Hz
  • Control: 2/3 point, or modulating 0(2)–10 V / 0(4)–20 mA
  • Power consumption: 1.5–2.5 W in operation
  • Angle of rotation: 0–90° (max 93°), L/R switchable
  • Position feedback: None or 2 SPDT
  • Protection: IP54, class II/III
  • Ambient: −30 to +50 °C
  • Life cycle: ≥70,000
  • Certification: CE, UKCA, RoHS

Order Code

Suffix L denotes low noise; SL denotes low noise with auxiliary switches.

Example: F30A-5D24-L — 5 Nm, 2/3 point, 24 V, low noise.

Note: Running times are roughly double the standard variant. Confirm this suits the control strategy before specifying.


F30A Series Fast Running Damper Actuator

Fast-running actuators are designed for HVAC applications where the damper must reach its commanded position significantly faster than with a conventional actuator.

They provide rapid and accurate positioning for applications requiring quick airflow adjustment, pressure control or system response, while retaining the same flexible control options available across the standard actuator range.

Find out more technical details about our F30A-Q

F30A Fast Runing Actuator

Torque and Running Time

Torque Damper area Running time Weight
5 Nm 1 m² 2.5–3.5 s 1.0 kg
10 Nm 2 m² 4–5 s 1.0 kg
16 Nm 4 m² 7–8 s 1.0 kg

Specification

  • Running time: 2.5–8 s depending on torque
  • Supply voltage: AC/DC 24 V or AC 230 V, 50/60 Hz
  • Control: 2/3 point, or modulating 0(2)–10 V / 0(4)–20 mA
  • Power consumption: 15 W in operation, 2 W at rest
  • Noise level: 55–60 dB
  • Angle of rotation: 0–90° (max 93°), L/R switchable
  • Protection: IP54, class II/III
  • Ambient: −30 to +50 °C
  • Life cycle: ≥30,000
  • Spindle: 12–26.7 mm
  • Certification: CE, UKCA, RoHS

Order Code

Suffix Q denotes fast running; SQ denotes fast running with auxiliary switches.

Example: F30A-16D24-Q — 16 Nm, 2/3 point, 24 V, fast running.

Note: Higher speed carries trade-offs — 15 W draw against 1.5–5 W for the standard unit, 55–60 dB against ≤45 dB, and a ≥30,000 cycle life against ≥70,000. Size the supply accordingly.


Control Signals and Wiring

All modulating F30A actuators use an onboard SW1 dial switch to select input signal type and feedback range, so a single model covers several control configurations.

Input signal Feedback Input resistance
DC 0–10 V DC 0–10 V 150 kΩ
DC 2–10 V DC 2–10 V 150 kΩ
DC 0–20 mA DC 0–10 V 500 Ω
DC 4–20 mA DC 2–10 V 500 Ω

Find out more about wiring and dimension for our F30A